1. Увод
The SINOTIMER STVP series automatic over-voltagе и под-волtage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltagе, под-волtage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.
This protector integrates multiple protection functions including over-voltagе, под-волtage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.
Детаљно упутство за употребу у PDF формату је доступно за преузимање: Упутство за употребу (ПДФ)
2. Кључне карактеристике
- Овер-волtagе заштита
- Ундер-волtagе заштита
- Заштита од прекомерне струје
- Аутоматски опоравак
- Волtage display (separate ABC phase voltagе мерење)
- Ampere display (separate ABC phase ampere measurement)
- Трофазни ampere unbalance protection
- Phase sequence protection (reverse phase protection)
- Zero line break protection
- Заштита од прекида фазе
- Fault inquiry function
- Rotation display of voltage and current for each phase
- Adjustable over-voltage protection value and recovery value
- Adjustable under-voltage protection value and recovery value
- Adjustable over-current protection value and action time
- Adjustable 3-phase ampere unbalance protection value and action time
- Adjustable delay time after power-on
- Подесиво време кашњења опоравка од грешке
- Factory data reset function
3. Спецификације производа
| Атрибут | Валуе |
|---|---|
| Број модела | STVP936-1-80A |
| Повер Суппли | 3*127V/220VAC 60Hz |
| Ратед Волtage | 220В |
| Фаза | Три фазе |
| Макс. Струја оптерећења | 1~80A Adjustable (default: 80A) |
| Овер-волtagе Заштитни опсег | 121V-150V-OFF Adjustable (default: 140V) |
| Овер-волtagе Опсег опоравка | 120V-149V (default: 135V) |
| Овер-волtage Action Time | 0.1~10 seconds (default: 0.2s) |
| Ундер-волtagе Заштитни опсег | 118V-80V-OFF Adjustable (default: 90V) |
| Ундер-волtagе Опсег опоравка | 118V-91V (default: 95V) |
| Ундер-волtage Action Time | 0.1~10 seconds (default: 0.2s) |
| 3-Phase Volt Unbalance Protection | 10%~50%~OFF (default: 20%) |
| 3-Phase Volt Unbalance Action Time | 0.1~10 seconds (default: 1s) |
| Delay Time After Power-on | 2~255 seconds (default: 2s) |
| Време кашњења опоравка од грешке | 2~600 seconds (default: 60s) |
| Приказ модела | ЛЦД |
| Димензије | 71.5mm (W) * 95.2mm (H) * 65.7mm (D) |
| Инсталација | 35 мм ДИН шина |
| Цертифицатион | ЦЕ, РоХС |
4. Безбедносне информације
- Инсталацију и одржавање треба да обављају само квалификовани електричари.
- Ensure the power supply is disconnected before any installation or wiring work.
- The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
- Проверите да ли су сви спојеви ожичења безбедни и исправни пре него што укључите напајање.
- Do not operate the device in wet or hazardous environments.
5. Инсталација
5.1 Физичке димензије

5.2 Монтажа
The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

5.3 Дијаграм ожичења
Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.


6. Подешавање и конфигурација
Да бисте ушли у режим подешавања, притисните и држите СЕТ button for 3 seconds. Then, continuously press СЕТ to cycle through the parameters. Use the ▲ и ▼ buttons to adjust the values. When "ENd" appears, press СЕТ again to save the data and exit the setting mode.
If no operation is performed within 10 seconds after pressing СЕТ, the device will automatically exit the setting mode, and any unsaved changes will be lost.
6.1 Parameter Settings Table
| Корак | Садржај | ЛЦД екран | Description / Range (Default) |
|---|---|---|---|
| 1 | Овер-волtagе вредност заштите | Uvo 280V | 221V-300V-OFF (280V) |
| 2 | Овер-волtagе повратна вредност | Uvor 250V | 220В-299В (250В) |
| 3 | Овер-волtage protection action time | 0.2С | 0.1-10с (0.2с) |
| 4 | Ундер-волtagе вредност заштите | Uve 160V | 219V-150V-OFF (160V) |
| 5 | Ундер-волtagе повратна вредност | Uver 180V | 151В-220В (180В) |
| 6 | Ундер-волtage protection action time | 0.2С | 0.1-10с (0.2с) |
| 7 | Вредност заштите од прекомерне струје | >In 80A | 1-80А (80А) |
| 8 | Over-current protection action time | 5S | 1-512с (5с) |
| 9 | 3 фаза amp unbalance protection value | >In % | 5%-90%-OFF (25%). Not active if current < 2A. |
| 10 | 3 фаза amp unbalance protection action time | 1.0 С | 0.1-10с (1с) |
| 11 | Заштита редоследа фаза | ON ABC | ON or OFF (ON) |
| 12 | Време одлагања укључивања | 2 С | 2-255с (2с) |
| 13 | Fault recovery delay time | 60 С | 2-512с (60с) |
| 14 | Fault inquiry code | E0 | Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage. |
| 15 | Крај | Крај | Press SET to save and exit. |
6.2 Ресетовање на фабричка подешавања
To reset the device to factory settings, press and hold the ▲ и ▼ тастери истовремено 3 секунде.
7. Операција
Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).
У случају преко-волtagе, под-волtage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.
КСНУМКС. Решавање проблема
8.1 Fault Inquiry
If a fault occurs, the device will display an error code (E0). You can press the ▲ button to query the last 5 fault records (E1-E5). The display will indicate:
- ">U" for overvoltagе догађаји.
- "<U" for undervoltagе догађаји.
8.2 Phase Sequence Error
If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.
9. Одржавање
- Држите уређај чистим и без прашине и влаге.
- Редовно проверавајте спојеве ожичења да ли постоје затегнутост и знаци хабања или оштећења.
- Do not attempt to repair the device yourself. Refer to qualified personnel for service.
10. Гаранција и подршка
For technical support, inquiries, or warranty claims, please contact the distributor:
Дистрибутер: XNY INTERNATIONAL LIMITED
Адреса: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
Тел: 0086 57761733853
факс: 0086 577 89736991
ВхатсАпп: 0086 1565857 3377
Вецхат: sinotimer
Скипе: sinotimer
Web: ввв.синотимер.цом
Емаил: info@sinotimer.com