Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign User Manual
Model: EDG 1 R EL M6
1. Увод
This manual provides comprehensive instructions for the installation, operation, and maintenance of the Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign. This edge-lit sign is designed for emergency egress lighting in commercial and institutional environments, ensuring clear visibility during power outagес.
The EDG 1 R EL M6 features a durable aluminum construction, energy-efficient LED illumination, and a reliable battery backup system. Adherence to these instructions will ensure proper function and compliance with safety standards.
2. Безбедносне информације
- Прочитајте сва упутства: Before beginning installation or maintenance, carefully read and understand all instructions provided in this manual.
- Искључите напајање: Always disconnect power at the circuit breaker before installing, servicing, or cleaning the unit. Failure to do so may result in electric shock or serious injury.
- Квалификовано особље: Installation, servicing, and testing must be performed by qualified personnel in accordance with all national and local electrical codes and safety regulations.
- Усклађеност са УЛ 924: This product is designed to meet UL 924 standards for emergency lighting and power equipment. Ensure all installations comply with these and other applicable standards.
- Руковање батеријама: The unit contains a sealed, maintenance-free nickel-cadmium battery. Do not attempt to open or service the battery. Dispose of batteries according to local regulations.
- Услови околине: Install in locations where ambient temperatures are within the specified operating range. Do not install near gas or electric heaters.
3. Садржај пакета
Проверите да ли су све компоненте присутне и неоштећене након отварања паковања:
- Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign (Battery-Powered, Red)
- Mounting Hardware (typically includes screws, anchors, and canopy)
- Instruction Sheet / Wiring Diagram
4. Подешавање и инсталација
The EDG 1 R EL M6 is designed for surface mounting. Ensure the mounting surface is structurally sound and capable of supporting the fixture's weight.
4.1 Опције монтаже
This unit supports various surface mounting configurations. Refer to the included wiring diagram for specific instructions on ceiling, wall, or end mounting.

Слика: Одозго надоле view of the Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign, showing the brushed aluminum housing and clear acrylic panel with red 'EXIT' letters.
4.2 Електричне везе
- Напајање: The unit is dual voltage (120/277V). Connect the appropriate AC power supply wires to the fixture's input terminals as indicated in the wiring diagram.
- Повезивање батерије: Ensure the internal battery is properly connected after wiring the AC power. The battery is typically pre-connected but may require a final plug-in during installation.
- Почетна наплата: After installation and power connection, allow the unit to charge for a minimum of 24 hours before conducting any tests. This ensures the nickel-cadmium battery reaches full capacity.

Слика: Са стране view of the Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign, highlighting its slim profile and edge-lit design.
5. Упутство за употребу
The Lithonia Lighting EDG 1 R EL M6 operates automatically once properly installed and charged.
- Нормалан рад: When AC power is present, the LED 'EXIT' letters will be illuminated. The internal battery will continuously charge to maintain readiness for emergency operation.
- Хитна операција: In the event of an AC power failure, the unit will automatically switch to battery power, illuminating the 'EXIT' letters for a minimum of 90 minutes.
- Дугме за тестирање: A test button is typically located on the side or bottom of the unit. Pressing this button simulates an AC power failure, allowing you to verify the emergency lighting function. The 'EXIT' letters should illuminate when the button is pressed and extinguish when released (assuming AC power is present).

Слика: Фронт view of the Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign, clearly showing the red 'EXIT' letters.
6. Одржавање
The EDG 1 R EL M6 is designed for low maintenance. However, regular checks are essential to ensure continued reliability.
- Месечно тестирање: Press the test button for at least 30 seconds to ensure the emergency lights operate.
- Годишње тестирање: Disconnect AC power to the unit for a full 90-minute discharge test. The unit should remain illuminated for the entire duration. Reconnect AC power after the test.
- Чишћење: Clean the exterior surfaces and acrylic panel with a soft, damp крпа. Не користите абразивна средства за чишћење или раствараче. Пре чишћења се уверите да је напајање искључено.
- Замена батерије: The nickel-cadmium battery is maintenance-free and has a long lifespan. If the unit fails to hold a charge or operate for the required 90 minutes during testing, the battery may need replacement by qualified service personnel.
- NFPA Compliance: All life safety equipment, including emergency lighting for paths of egress, must be maintained, serviced, and tested in accordance with all National Fire Protection Association (NFPA) and local codes.
КСНУМКС. Решавање проблема
If your EDG 1 R EL M6 LED Emergency Exit Sign is not functioning as expected, refer to the following common issues and solutions:
| Проблем | Могући узрок | Решење |
|---|---|---|
| 'EXIT' letters do not illuminate during AC power failure. | Battery not charged or faulty; AC power not connected. | Ensure AC power is connected and allow 24 hours for initial charge. If problem persists, battery may need replacement. |
| 'EXIT' letters do not illuminate when test button is pressed. | Battery not connected or faulty; unit not receiving AC power. | Verify AC power connection. Check battery connection. Allow 24 hours for charge. |
| Unit does not stay illuminated for 90 minutes during annual test. | Battery capacity reduced due to age or defect. | Battery needs replacement. Contact qualified service personnel. |
| 'EXIT' letters are dim. | Low battery charge; dirty acrylic panel. | Allow unit to charge for 24 hours. Clean the acrylic panel. |
For issues not listed above, or if troubleshooting steps do not resolve the problem, contact Lithonia Lighting customer support or a qualified electrician.
8. Спецификације
Detailed technical specifications for the Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign:
- Број модела: EDG 1 R EL M6
- Број дела: LTHEDG1RELM6
- Произвођач: Литхониа Лигхтинг
- Димензије: Approximately 13 inches (Width) x 11.12 inches (Height)
- Тежина артикла: 2.2 фунте (1 килограм)
- Боја: Red (letters)
- Стил: Напаја се батеријама
- завршити: брушени алуминијум
- Материјал: Aluminum (housing), Acrylic (panel)
- Извор напајања: AC (for charging)
- Волtage: 120/277V (Dual Voltage)
- Ватtage: 3 вати
- Тип сијалице: ЛЕД
- Тип монтаже: Surface Mount (Ceiling, Wall, End)
- сертификација: УЛ Листед
- батерија: Sealed, maintenance-free Nickel-Cadmium
- Emergency Operation Duration: Минимум 90 минута
- ЛЕД Лamp живот: До 100,000 сати
- Letter Height: 6 инча
- Stroke Width: 3/4 инча
- Viewинг Удаљеност: 100 feet (UL 924 standard)

Image: Lithonia Lighting EDG 1 R EL M6 LED Emergency Exit Sign with key dimensions indicated.
9. Гаранција и подршка
For detailed warranty information, product registration, or technical support, please visit the official Lithonia Lighting webсајт или контактирајте њихову службу за кориснике. Сачувајте рачун за куповину за потребе гаранције.
Lithonia Lighting Customer Service: Refer to the contact information provided on the product packaging or the official brand webсајту.