1. Увод

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A. Please read this manual thoroughly before installation and operation to ensure proper functionality and to prevent damage or injury.

The ATS is designed to provide uninterrupted power by automatically transferring loads between phases in a three-phase supply system. It features intelligent monitoring and protection against phase failure, over/under voltage, and overcurrent conditions, ensuring the stability and safety of connected equipment.

2. Безбедносне информације

УПОЗОРЕЊЕ: Опасност од струјног удара. Инсталацију и сервисирање треба да обавља само квалификовано особље.

  • Always disconnect power before installing or servicing the ATS.
  • Уверите се да су све инсталације у складу са локалним и националним електричним прописима.
  • Проверите тачан обимtage and current ratings before connecting the device.
  • Не користите уређај ако изгледа оштећено.
  • Држите децу даље од електричних уређаја.

3. Производ је готовview

The EARU Electric 3-Phase ATS is an intelligent device that continuously monitors your three-phase power supply. It automatically switches single-phase loads to a healthy phase in case of a phase failure or imbalance, ensuring continuous operation of critical equipment.

3.1. Садржај пакета

  • 1 x EARU Electric 3-Phase Auto Transfer Switch (ATS)

3.2. Front Panel and Indicators

Front panel of EARU Electric 3-Phase ATS with digital display and control buttons

Опис слике: The front panel of the ATS features a digital display showing voltage for L1, L2, L3 phases and current for L1. Below the display are indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I). Control buttons include 'SET' (Menu key), 'Digit+/Up', 'Digit-/Down', and 'Manual ON/OFF' (Power button).

The digital display provides real-time voltage readings for each phase (L1, L2, L3) and the current for L1. Status indicators alert you to the operational state and any detected faults:

  • Снага: Output indication.
  • >V: Овер-волtagе индикација.
  • <V: Ундер-волtagе индикација.
  • >ја: Over-current indication.

Control buttons allow for parameter settings and manual operation:

  • КОМПЛЕТ: Menu key for accessing settings.
  • Digit+/Up: Increases value or navigates up in menus.
  • Digit-/Down: Decreases value or navigates down in menus.
  • Ручно укључивање/искључивање: Power button for manual control.

4. Подешавање и инсталација

The ATS is designed for standard DIN rail mounting. Ensure sufficient space for ventilation and wiring connections.

4.1. Dijagram ožičenja

Wiring diagram for EARU Electric 3-Phase ATS showing input and output connections

Опис слике: A detailed wiring diagram illustrates the connection points for the ATS. The top terminals are labeled 'IN' with connections for N, L1, L2, L3. The bottom terminals are labeled 'OUT' with connections for N and L1. The diagram shows how to connect the three-phase input to the ATS and how a single-phase load (L1 and N) is connected to the output, with internal connections for phase monitoring and switching.

Follow the wiring diagram carefully. Incorrect wiring can lead to device malfunction or electrical hazards.

  • Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals.
  • Connect the single-phase load (N, L1) to the 'OUT' terminals. The ATS will manage the phase transfer for the L1 output.
  • Ensure all connections are secure and tightened to prevent loose contacts and overheating.

4.2. Почетно укључивање

After completing the wiring, restore power to the system. The ATS will power on and begin monitoring the phases. The digital display will show the current voltage readings for each phase. If all phases are stable and within acceptable limits, the ATS will provide power to the output.

5. Упутство за употребу

The ATS operates automatically, but you can adjust its protection parameters to suit your specific requirements.

5.1. Understanding the Display and Indicators

The digital display continuously shows the real-time voltage of each phase (L1, L2, L3) and the current on L1. The indicator lights provide quick visual feedback on the device's status and any detected anomalies.

Close-up of EARU Electric 3-Phase ATS digital display showing voltage and current readings

Опис слике: Крупни план view of the ATS digital display. It shows '220V' for L1, L2, and L3, and '63.0A' for L1 current. Below these readings are small indicator icons for Power, >V (Over-voltage), <V (Under-voltage), and >I (Over-current).

5.2. Adjusting Protection Parameters

Use the 'SET' button to enter the parameter setting mode. Use the 'Digit+/Up' and 'Digit-/Down' buttons to navigate through settings and adjust values. Press 'SET' again to confirm and save changes.

Adjustable Protection Parameters
ПараметарОпсег подешавањаПодразумевана поставка
Over Current Protection Setting Range1-63А/100А30А
Continuous Over Current Protection Times0-20 ТимесОФФ
Овер Волtage Protection Setting Range230-300В270В
Овер Волtage Protection Recover Setting Range225-295В265В
Ундер Волtage Protection Setting Range140-210В170В
Ундер Волtage Protection Recover Setting Range145-215В175В
Волtage & Current Protection Recover Delay1-500с30-их

5.3. Automatic Phase Transfer

The ATS automatically monitors the three input phases (L1, L2, L3). If a phase failure or significant voltage imbalance (over/under voltage) is detected on the currently supplying phase, the device will automatically transfer the single-phase output load to a healthy, stable phase within the same supply. This process is designed to be seamless and rapid, minimizing power interruption to connected equipment.

5.4. Automatic Recovery

Once the primary phase recovers and stabilizes, the ATS will intelligently switch the load back to the primary source, ensuring optimal power distribution and preventing equipment damage from unstable power. The recovery delay can be configured as per your operational needs.

6. Одржавање

The EARU Electric ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.

  • Чишћење: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Провере везе: Periodically inspect all wiring connections to ensure they remain tight and free from corrosion.
  • Услови животне средине: Уверите се да радно окружење остаје у наведеним опсезима температуре и влажности.

КСНУМКС. Решавање проблема

If you encounter issues with your ATS, refer to the following common problems and solutions:

Решавање проблема за
ПроблемМогући узрокРешење
Нема излазне снагеNo input power; all phases unstable; device in fault state.Check incoming power supply. Verify all phases are stable. Check fault indicators.
">V" or "<V" indicator litОвер-волtagе или под-волtage detected on a phase.Проверите инпут волtage stability. The ATS will automatically transfer if another phase is healthy.
">I" indicator litOver-current detected on the output.Reduce load on the output. Check for short circuits in the connected equipment.
Device not transferring phasesNo healthy alternative phase available; transfer delay setting too long.Ensure at least one healthy phase is present. Check and adjust the transfer delay settings.
Дигитални дисплеј не радиNo power to the device; internal fault.Check power supply. If power is present and display is off, contact support.

For issues not covered here, please contact EARU customer support.

8. Спецификације

Detailed specifications and dimensions of EARU Electric 3-Phase ATS

Опис слике: This image displays the physical dimensions of the ATS (90mm width, 96mm height, 66mm depth) and a table of detailed technical specifications, including current rating, voltage, frequency, and various protection setting ranges.

ФеатуреДетаљ
БрандЕАРУ
Број моделаEARU-1012
Оперативни режимОН-ОФФ
Цуррент Ратинг63 Amps
Оператинг Волtage440 Volts (AC 3*220V (N-L1/L2/L3))
Називна фреквенција50/60Хз
Тип контактаНормално отворен
Тип конектораStandard DIN rail 63A
Цирцуит Типе4-ваи
Контакт материјалБакар
Over Current Protection Setting Range1-63A/100A (Default 30A)
Continuous Over Current Protection Times0-20 Times (Default OFF)
Овер Волtage Protection Setting Range230-300V (Default 270V)
Овер Волtage Protection Recover Setting Range225-295V (Default 265V)
Ундер Волtage Protection Setting Range140-210V (Default 170V)
Ундер Волtage Protection Recover Setting Range145-215V (Default 175V)
Волtage & Current Protection Recover Delay1-500s (подразумевано 30s)
Тежина артикла450 г
Димензије пакета15 к 15 к 15 цм
Земља пореклаИндија

9. Гаранција и подршка

9.1. Информације о гаранцији

The EARU Electric 3-Phase Auto Transfer Switch (ATS) comes with a 1-годишња гаранција произвођача from the date of purchase. This warranty covers defects in materials and workmanship under normal use. It does not cover damage caused by improper installation, misuse, accidents, or unauthorized modifications.

9.2. Корисничка подршка

For technical assistance, warranty claims, or any questions regarding your EARU Electric ATS, please contact your retailer or the manufacturer directly. Ensure you have your product model number (EARU-1012) and proof of purchase available when contacting support.

Повезани документи - EARU-1012

Преview Automatic Transfer Switch Operating Instructions - EARU ATS
Detailed operating instructions and technical specifications for the EARU Automatic Transfer Switch (ATS), covering product overview, working conditions, installation, maintenance, and wiring.
Преview EARU GFGQX-63 Three-Phase Digital Adjustable Reclosing Protector User Manual
User manual for the EARU GFGQX-63 Three-Phase Digital Adjustable Reclosing Protector. This device provides over/under voltage, over current, phase sequence, and phase imbalance protection with automatic reclosing functionality. Includes detailed specifications, settings, and wiring instructions.
Преview EARU Automatic Transfer Switch (ATS) Operating Instruction and Technical Specifications
Comprehensive operating instructions and technical specifications for the EARU Automatic Transfer Switch (ATS) model EAATS-F-CG-80. Covers product overview, working conditions, model breakdown, detailed technical parameters, installation guidelines, maintenance procedures, and wiring diagrams.
Преview EARU EAPDX-40/63 Series Adjustable VoltagУпутство за употребу заштитника е и струје
User manual for the EARU EAPDX-40/63 Series Adjustable Voltage & Current Protector, detailing specifications, features, and operation for electrical protection. Includes setup instructions and parameter configuration.
Преview EARU-X6/8 Metal LED Indicator Light Instruction Manual
User manual for EARU-X6/8 series Metal LED Indicator Lights, detailing safety instructions, warnings, and product description for reliable status indication in industrial and traffic applications.
Преview EARU KR0548-CH WiFi Smart Automatic Transfer Switch (ATS) User Manual
User manual for the EARU KR0548-CH WiFi Smart Automatic Transfer Switch (ATS). Learn how to install, connect, and operate the device using the EARU app for seamless switching between main and backup power sources.